Diagnosing GenSet Low Power Output

  In this installment of our maintenance series, we diagnose low engine power output on a Northern Lights 12kW generator. This engine is unable to produce more than 7kw of power, but can reliably deliver that, and otherwise is running fairly well. We walk through the diagnostic procedure checking for intake blockage, fuel system problems,…

Ardnamurchan Point

Ardnamurchan Point, along the eastern shore of the Sea of the Hebrides, is the westernmost point on mainland Britain. The name derives from the Scottish Gaelic term Ard na Murchan, meaning “the hill of the great sea”. Rounding Ardnamurchan Point is considered a major milestone for cruising boaters. Currents can run 1.5kts around the point…

Replacing Generator Overhead Light

The overhead space between our generator and the ceiling is rather limited, and the fluorescent light mounted directly above it consumed a large chunk of that. So much so that James recently broke a bulb when jammed over top working to free the exhaust elbow from the exhaust hose. So we decided to remove the…

Changing Starter in 12kW Northern Lights

  Our Northern Lights 12kW generator is just a slight bit slower to start. In this video, we check the likely possibilities for slow to start, including air filters, fuel filters, voltage at battery, and voltage at starter during cranking and determine that the starter is at fault. We then show the process of changing…

Gometra Harbour

More than two months after we dropped anchor off the Isle of Gigha, we departed north for Stornoway to refuel and replenish our deep stores. The anchorage had worked out well and the islanders had taken good care of us, but this was by far the longest we’d ever been at anchor in any one…

Essentials at Gigha

After 8 weeks at Gigha, and 63 days since we’d last provisioned, we’d consumed all our fresh fruit, were almost out of fresh vegetables and our deep stores were dwindling. So when Joe Teale at Ardminish Stores on Gigha contacted us to ask if we needed anything, we gratefully accepted his offer. Duncan and the…

Gen Rear Main Oil Seal

Our generator showed a light misting of oil around the generator cooling fan a month back. At just under 7,000 hours, it’s a bit early to be leaking, but it’s not a huge issue since rear main oil seals don’t fail catastrophically nor even quickly. It just means that in the next year or so,…

Maintaining at Gigha

While our cruising lifestyle may be on pause during the Scottish lockdown, our maintenance log isn’t. Several scheduled service items came due in mid-May, including annual testing, lubricating and changing the oil and filter in our gasoline engines, changing the hydraulic zincs, and charging our backup batteries. We also completed some unscheduled maintenance work, such…

Load Shedding

One of the challenges with the smaller electrical systems found on most boats is managing the power load. Whenever electrical loads are running on a boat, they are delivered by some power source. It might be the generator, it could be shore power, or it could be the inverter. But, whatever the power source, it…

Water Leak

Saturday morning we lifted the floor covering in the master stateroom head to access stores and found the floor underneath soaked wall-to-wall. We opened up the storage area below and it also had a lot of water in it. The first task was to get everything out of the storage areas and all dried and…